Unstable Temperature And Humidity Control in Cleanroom Construction Of Hollow Capsule Production Lines

Feb 10, 2026

Leave a message

Unstable temperature and humidity control is one of the most prominent and critical problems encountered in the construction of cleanrooms for hollow capsule production lines. Hollow capsules, mainly made of gelatin, hydroxypropyl methylcellulose (HPMC) and other raw materials, are extremely sensitive to environmental humidity, and temperature fluctuations also have a direct impact on their forming quality and stability, which has become a key contradiction between cleanroom construction and actual production needs.

 

In terms of humidity sensitivity, the moisture content of hollow capsules has strict standard requirements during the production process. If the humidity in the cleanroom is too low (usually lower than 40%), the raw materials such as gelatin will lose moisture rapidly during the dipping, drying and forming stages, resulting in insufficient toughness of the capsule shell. This will easily lead to problems such as brittleness, cracking, edge breaking and fragmentation during the subsequent cutting, fitting, packaging and transportation processes, greatly reducing the qualified rate of finished products. On the contrary, if the humidity in the cleanroom is too high (higher than 60% in general), the capsule shell will absorb excess moisture from the air, resulting in softening, deformation, poor shape retention and adhesion between capsule shells. In severe cases, it will cause the capsule to be unable to fit normally, or even mildew due to excessive moisture during storage, which will not only affect the product quality, but also bring potential safety hazards to the subsequent drug filling.

 

The root cause of unstable humidity control is mostly the insufficient dehumidification capacity of the air conditioning system in the cleanroom during the construction stage. On the one hand, the design of the air conditioning dehumidification system does not fully consider the particularity of hollow capsule production. The dehumidification equipment selected is not matched with the production scale, the dehumidification efficiency is low, and it is impossible to quickly adjust the humidity in the workshop when the environmental humidity changes or the production process emits moisture (such as the moisture volatilization during the glue mixing and dipping process). On the other hand, the air conditioning system lacks an efficient and stable humidity control system, and the sensor layout is unreasonable, resulting in inaccurate humidity detection, delayed adjustment response, and large fluctuations in indoor humidity (even exceeding the allowable fluctuation range of ±5% in the production process).

 

Temperature fluctuations in the cleanroom will further exacerbate the instability of product quality. The optimal temperature range for hollow capsule production is usually 20-24℃. If the temperature is too high, it will accelerate the volatilization rate of moisture in the glue solution, affect the uniformity of the capsule shell thickness during the dipping process, and easily cause the capsule shell to be too thin or uneven; at the same time, high temperature will also accelerate the aging of raw materials such as gelatin, reducing the mechanical strength of the capsule shell. If the temperature is too low, the fluidity of the glue solution will decrease, resulting in insufficient dipping amount, too thick capsule shell, and affecting the fitting accuracy of the capsule. In actual production, the unstable temperature control is often accompanied by the unreasonable design of the air supply and return air system in the cleanroom, such as uneven air supply, dead corners of air flow, and poor heat exchange efficiency of the air conditioning system, which leads to uneven temperature distribution in different areas of the workshop (such as the temperature difference between the dipping area and the drying area exceeding 3℃), making it difficult to ensure the consistency of product quality in the whole production line.

 

It should be emphasized that the unstable control of temperature and humidity is not only a problem of cleanroom construction, but also directly restricts the normal operation of the hollow capsule production line and the stability of product qualification rate. Compared with other problems in cleanroom construction (such as inconsistent cleanliness level, unreasonable equipment layout), temperature and humidity control involves the coordination of multiple links such as equipment selection, system design, sensor layout and operation adjustment during the construction stage. Once the construction is completed, the transformation of the air conditioning dehumidification and temperature control system requires high cost and long cycle, which will seriously affect the normal production progress. Therefore, it is particularly important to fully consider the temperature and humidity requirements of hollow capsule production in the early design and construction stage of the cleanroom, select matching dehumidification and temperature control equipment, optimize the system design, and ensure the stability and accuracy of temperature and humidity control, so as to avoid the contradiction between cleanroom construction and production needs.